{"id":3994,"date":"2026-11-11T17:00:00","date_gmt":"2026-11-11T09:00:00","guid":{"rendered":"https:\/\/cnbygele.com\/?p=3994"},"modified":"2026-11-12T12:43:10","modified_gmt":"2026-11-12T04:43:10","slug":"active-harmonic-filter-ct-saturation","status":"publish","type":"post","link":"https:\/\/cnbygele.com\/pt\/blog\/active-harmonic-filter-ct-saturation\/","title":{"rendered":"Satura\u00e7\u00e3o do TC do Filtro Ativo de Harm\u00f3nicas: Reconhecer Sinais de Feedback Distorcidos"},"content":{"rendered":"<p>Active harmonic filter CT saturation is a measurement problem in which a current transformer no longer reproduces the primary current faithfully under the actual operating condition. Suspect it when the filter&#8217;s current feedback becomes increasingly inconsistent with a suitable independent measurement as load changes, but do not diagnose it from high THD or a flattened waveform alone. First verify CT identity, ratio, polarity, phase mapping, measurement location, secondary burden, and instrument bandwidth. Establish whether distortion belongs to the primary load current, the CT, or another part of the measurement chain before changing filter capacity or settings.<\/p>\n<h2>Why distorted feedback matters<\/h2>\n<p>An AHF uses current information as part of its compensation process. If the measurement path misrepresents the current, an apparently reasonable setting can operate on misleading evidence. The observed result may resemble an undersized filter, an incorrect ratio, an unsuitable control boundary, or a changing load. Those possibilities require different remedies. Replacing the filter or adjusting compensation priorities before checking the feedback can leave the initiating problem unresolved.<\/p>\n<p>This guide focuses on the distinction between CT saturation and other feedback errors. It complements the <a href=\"https:\/\/cnbygele.com\/blog\/active-harmonic-filter-ct-ratio\/\">AHF CT ratio investigation<\/a> and the <a href=\"https:\/\/cnbygele.com\/blog\/active-harmonic-filter-ct-placement-wiring\/\">CT placement and wiring guide<\/a>. It does not provide a universal saturation threshold, approve a particular CT replacement, or authorize testing an energized secondary circuit by disconnecting it.<\/p>\n<h2>Establish which measurement path is installed<\/h2>\n<p>Record the actual AHF model, the specified sensing arrangement, CT identification, selected tap where applicable, primary and secondary ratings, input compatibility, and the approved installation drawing. Confirm whether the system uses conventional current-output CTs or another documented sensor arrangement. Procedures suitable for one sensor type must not be transferred to another simply because both measure current.<\/p>\n<p>Use the <a href=\"https:\/\/cnbygele.com\/product\/ahf-active-harmonic-filter-harmonic-control\/\">CNBYG active harmonic filter product information<\/a> and the delivered manual to establish the applicable equipment boundary. This article does not claim that every CNBYG variant uses an identical input or an internal saturation-detection algorithm. Obtain the specified sensor requirements, permissible secondary loading, and frequency-response information before evaluating substitutes.<\/p>\n<h2>Distinguish primary distortion from measurement distortion<\/h2>\n<p>Nonlinear loads can draw a distorted primary-current waveform during normal operation. Seeing a nonsinusoidal curve on a display therefore does not prove CT saturation. Compare the installed feedback with a suitable independent measurement of the same primary current and time interval. The reference instrument and sensor must have appropriate range, bandwidth, crest-factor capability, and installation conditions for the comparison to be meaningful.<\/p>\n<p>An <a href=\"https:\/\/www.ipstconf.org\/papers\/Proc_IPST2021\/21IPST102.pdf\" rel=\"noopener nofollow\" target=\"_blank\">IPST research paper on CT saturation detection<\/a> examines distorted secondary signals and reconstruction methods in a protection-system test context. It supports the general point that saturation changes the reproduced signal. Its studied network, algorithms, and numerical results are not specifications for a CNBYG AHF. Do not copy the paper&#8217;s test thresholds into a field controller or assume that a protection experiment establishes the behavior of an AHF feedback input.<\/p>\n<h2>Use symptoms as hypotheses rather than verdicts<\/h2>\n<p>The following table separates fault paths that can look similar on a dashboard. It is a qualitative evidence guide. No row provides an automatic diagnosis, and the absence of a visible symptom does not certify a sensor. Check the installed equipment documentation and the comparison method before assigning a cause.<\/p>\n<div style=\"overflow-x:auto;max-width:100%\">\n<table style=\"border-collapse:collapse;width:100%;min-width:640px;table-layout:fixed\">\n<thead>\n<tr>\n<th style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Observed pattern<\/th>\n<th style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Possible explanation<\/th>\n<th style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Evidence to compare<\/th>\n<th style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Avoid the shortcut<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Nearly constant proportional difference over several loads<\/td>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Ratio or scaling mismatch<\/td>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">CT identity, selected tap, configured ratio and simultaneous readings<\/td>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Changing the ratio to hide a load-dependent error<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Agreement at one load but increasing divergence at another<\/td>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">CT capability, burden, bandwidth or measurement-chain limit<\/td>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Comparable waveforms and instrument ranges at both conditions<\/td>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Declaring saturation from one RMS value<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Sign or phase relationship is inconsistent<\/td>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Polarity, mapping or reference mismatch<\/td>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Approved phase references and the complete signal path<\/td>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Treating every sign error as saturation<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Both independent primary measurement and feedback show similar distortion<\/td>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Actual nonlinear load current<\/td>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Matched time window, spectrum and sensor suitability<\/td>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Calling all distorted current a CT fault<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Feedback clips while the independent reference does not<\/td>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Sensor or input-chain limitation<\/td>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">CT loading, input range, waveform capture and documentation<\/td>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Assuming the CT is the only possible limiting component<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Compensation remains limited with credible feedback<\/td>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Filter capacity, settings or operating boundary<\/td>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Output-limit status and measured load conditions<\/td>\n<td style=\"border:1px solid #d1d5db;padding:10px;text-align:left;vertical-align:top;white-space:normal;overflow-wrap:anywhere\">Buying a CT before checking the filter&#8217;s actual duty<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<p><figure><img decoding=\"async\" alt=\"Active harmonic filter measurement feedback investigation \u2014 isolated inspection planning\" class=\"wp-image-3992\" height=\"1024\" loading=\"lazy\" src=\"https:\/\/cnbygele.com\/wp-content\/uploads\/2026\/11\/active-harmonic-filter-ct-saturation-inspection-20261112.png\" style=\"max-width:100%;height:auto\" width=\"1536\" srcset=\"https:\/\/cnbygele.com\/wp-content\/uploads\/2026\/11\/active-harmonic-filter-ct-saturation-inspection-20261112.png 1536w, https:\/\/cnbygele.com\/wp-content\/uploads\/2026\/11\/active-harmonic-filter-ct-saturation-inspection-20261112-300x200.png 300w, https:\/\/cnbygele.com\/wp-content\/uploads\/2026\/11\/active-harmonic-filter-ct-saturation-inspection-20261112-1024x683.png 1024w, https:\/\/cnbygele.com\/wp-content\/uploads\/2026\/11\/active-harmonic-filter-ct-saturation-inspection-20261112-768x512.png 768w, https:\/\/cnbygele.com\/wp-content\/uploads\/2026\/11\/active-harmonic-filter-ct-saturation-inspection-20261112-18x12.png 18w, https:\/\/cnbygele.com\/wp-content\/uploads\/2026\/11\/active-harmonic-filter-ct-saturation-inspection-20261112-600x400.png 600w\" sizes=\"auto, (max-width: 1536px) 100vw, 1536px\" \/><figcaption>Product-reference illustration of Active Power Filter (APF) &amp; Active Harmonic Filter (AHF). The equipment is unconnected; no energized test or internal arrangement is shown.<\/figcaption><\/figure>\n<\/p>\n<h2>Check the complete secondary burden<\/h2>\n<p>For a conventional current-output CT, the connected secondary circuit includes more than the named instrument input. Leads, terminals, test facilities, and any approved connected devices contribute to the load presented to the CT. Compare the complete arrangement with the CT and AHF requirements. A change in cable route or an added device can matter even if the configured ratio remains unchanged.<\/p>\n<p>The <a href=\"https:\/\/www.eit.edu.au\/resources\/practical-electrical-metering-measurement-and-instrument-transformers\/\" rel=\"noopener nofollow\" target=\"_blank\">Engineering Institute of Technology&#8217;s metering material<\/a> discusses instrument-transformer characteristics and saturation behavior. Use such material for the underlying measurement principles; the installed CT data and AHF instructions determine suitability. Do not infer a harmonic-frequency accuracy specification from a fundamental-frequency class label alone, or assume that a protection CT and an AHF measurement CT are interchangeable.<\/p>\n<p>As an illustrative resistive calculation, secondary burden power is I\u00b2R. If the complete resistive loop were 0.20 ohm, 5 A would correspond to 5 VA, while 1 A would correspond to 0.20 VA. These are hypothetical inputs, not CNBYG specifications or permitted burden values. Real evaluation may also need reactive impedance and frequency-dependent effects. The comparison does not authorize replacing a 5 A input sensor with a 1 A sensor; input compatibility must be established separately.<\/p>\n<h2>Look for limits elsewhere in the signal chain<\/h2>\n<p>The sensor is not the entire measurement system. An input circuit, conversion stage, display scale, sampling arrangement, or data export can impose its own limitations. Establish what the displayed waveform represents and whether any averaging or filtering is applied. A plotted line with a flat top can result from several mechanisms, including display clipping or inadequate reference-instrument range.<\/p>\n<p>Record the instrument range and capture settings alongside each comparison. If the reference meter changes range between observations, check whether the resulting readings remain directly comparable. Do not compare a slow RMS display with a short transient capture as though they describe the same event. Preserve original data and identify the processing used to produce a spectrum or trend so that the reasoning can be reviewed later.<\/p>\n<h2>Plan observations across representative loads<\/h2>\n<p>Select operating conditions that are normal and permitted for the installation. Capture a moderate-load condition and the condition associated with the suspected fault where it can be observed safely. Record which loads are running, the AHF operating state, output-limit indications, and the locations of all measurements. Do not create an overload or a fault to provoke CT saturation during a general troubleshooting visit.<\/p>\n<p>Compare simultaneous evidence wherever practical. An independent clamp measurement made before a large drive starts cannot validate a feedback value recorded afterward. For intermittent events, preserve a common time basis or document the uncertainty between instruments. Record the current waveform, the relevant harmonic information, and the load state together. High THD alone is not a universal threshold for CT saturation or thermal failure, and this guide provides no arbitrary percentage at which a CT must fail.<\/p>\n<h2>Preserve the CT safety boundary<\/h2>\n<p>A conventional current-transformer secondary must not be opened while primary current can flow. Before disturbing a secondary circuit, use the approved isolation, shorting, and test arrangements specified for the installation. Do not unplug sensing leads, insert an unapproved meter in series, or apply an insulation tester across an electronic AHF input as an improvised check. Identify the sensor type before selecting any test method.<\/p>\n<p><a href=\"https:\/\/www.osha.gov\/laws-regs\/regulations\/standardnumber\/1910\/1910.333\" rel=\"noopener nofollow\" target=\"_blank\">OSHA 1910.333<\/a> addresses electrical isolation and verification within its scope. Apply the site&#8217;s governing electrical safety procedures and use qualified personnel for necessary energized observations. An AHF stop command does not establish that its supply or external sensing circuit is isolated. The primary conductor can remain energized even when the filter itself is not compensating.<\/p>\n<h2>Select a remedy from verified evidence<\/h2>\n<p>If the investigation confirms an incorrect ratio or phase mapping, correct that documented configuration issue and repeat the comparison. If the connected burden is unsuitable, resolve it through the approved circuit design. If the CT is unsuitable for the measured duty or required frequency response, select a replacement jointly with the AHF and sensor suppliers. Do not increase the CT primary rating merely to make a displayed error disappear without assessing the resulting measurement performance.<\/p>\n<p>Where a signal-chain limit remains uncertain, provide the supplier with the actual captures and configuration rather than adjusting unrelated compensation parameters. A review of <a href=\"https:\/\/cnbygele.com\/blog\/active-harmonic-filter-not-reducing-thd\/\">AHF compensation performance<\/a> should distinguish a measurement problem from an output-capacity or network-boundary problem. Keep any operating restriction visible until the approved remedy has been tested.<\/p>\n<p><figure><img decoding=\"async\" alt=\"Active harmonic filter measurement feedback investigation \u2014 documented equipment review\" class=\"wp-image-3993\" height=\"1024\" loading=\"lazy\" src=\"https:\/\/cnbygele.com\/wp-content\/uploads\/2026\/11\/active-harmonic-filter-ct-saturation-records-20261112.png\" style=\"max-width:100%;height:auto\" width=\"1536\" srcset=\"https:\/\/cnbygele.com\/wp-content\/uploads\/2026\/11\/active-harmonic-filter-ct-saturation-records-20261112.png 1536w, https:\/\/cnbygele.com\/wp-content\/uploads\/2026\/11\/active-harmonic-filter-ct-saturation-records-20261112-300x200.png 300w, https:\/\/cnbygele.com\/wp-content\/uploads\/2026\/11\/active-harmonic-filter-ct-saturation-records-20261112-1024x683.png 1024w, https:\/\/cnbygele.com\/wp-content\/uploads\/2026\/11\/active-harmonic-filter-ct-saturation-records-20261112-768x512.png 768w, https:\/\/cnbygele.com\/wp-content\/uploads\/2026\/11\/active-harmonic-filter-ct-saturation-records-20261112-18x12.png 18w, https:\/\/cnbygele.com\/wp-content\/uploads\/2026\/11\/active-harmonic-filter-ct-saturation-records-20261112-600x400.png 600w\" sizes=\"auto, (max-width: 1536px) 100vw, 1536px\" \/><figcaption>Product-reference illustration of Active Power Filter (APF) &amp; Active Harmonic Filter (AHF). The equipment is unconnected; no energized test or internal arrangement is shown.<\/figcaption><\/figure>\n<\/p>\n<h2>Verify the complete system after correction<\/h2>\n<p>Repeat the relevant measurements with the same locations, instrument settings, and comparable load states. Confirm that the feedback now agrees with the accepted reference within the project&#8217;s documented criteria. Then verify the AHF response under the approved commissioning plan. A corrected current indication does not, by itself, establish compliance at the point of common coupling or prove that every harmonic target has been met.<\/p>\n<p>Retain the CT and AHF identities, approved specifications, burden assessment, settings record, before-and-after captures, and final release decision. State what was confirmed and which intermittent conditions remain unobserved. If components or wiring changed, update the approved drawing and the spare-parts information. This prevents a later maintenance substitution from recreating the same mismatch while preserving an apparently familiar ratio setting.<\/p>\n<h2>Research background: distorted CT signals<\/h2>\n<p>The IPST 2021 presentation linked from the conference&#8217;s proceedings accompanies research into CT saturation detection and signal reconstruction. It is included as technical background on why a reproduced current signal can become unreliable. Its protection-system experiment does not establish a built-in AHF function, a field calibration procedure, or an approved software modification for this product.<\/p>\n<div style=\"position:relative;padding-bottom:56.25%;height:0;overflow:hidden\"><iframe allowfullscreen=\"\" loading=\"lazy\" src=\"https:\/\/www.youtube-nocookie.com\/embed\/7Bnjq-8lU18\" style=\"position:absolute;top:0;left:0;width:100%;height:100%;border:0\" title=\"IPST 2021 - LUIS G. GARCETE ALDERETE\"><\/iframe><\/div>\n<p><a href=\"https:\/\/www.youtube.com\/watch?v=7Bnjq-8lU18\" rel=\"noopener nofollow\" target=\"_blank\">Watch the educational lesson<\/a><\/p>\n<h2>Frequently asked questions<\/h2>\n<h3>Does high THD prove that a CT is saturated?<\/h3>\n<p>No. Primary load current can be distorted without CT saturation. Compare the installed feedback with a suitable independent measurement under the same operating condition and investigate the complete measurement chain.<\/p>\n<h3>Can I compensate for saturation by changing the CT ratio setting?<\/h3>\n<p>No. A ratio setting does not restore missing or distorted waveform information. Establish whether the problem is a fixed scaling mismatch, a sensor limitation, burden, or another signal-chain issue before choosing a remedy.<\/p>\n<h3>Can the same CT be used for an AHF and another instrument?<\/h3>\n<p>Only if the complete arrangement is explicitly supported by the relevant equipment specifications and approved design. Evaluate input compatibility, wiring, total burden, and safety requirements; do not add a device to an existing secondary circuit by assumption.<\/p>\n<h3>Is an AHF stop command enough before disconnecting CT leads?<\/h3>\n<p>No. Stopping compensation does not establish isolation of the primary conductor or the sensing circuit. Follow the installation&#8217;s approved CT safety and electrical isolation procedures before disturbing any connections.<\/p>\n<p><script type=\"application\/ld+json\">{\"@context\": \"https:\/\/schema.org\", \"@type\": \"FAQPage\", \"mainEntity\": [{\"@type\": \"Question\", \"name\": \"Does high THD prove that a CT is saturated?\", \"acceptedAnswer\": {\"@type\": \"Answer\", \"text\": \"No. Primary load current can be distorted without CT saturation. Compare the installed feedback with a suitable independent measurement under the same operating condition and investigate the complete measurement chain.\"}}, {\"@type\": \"Question\", \"name\": \"Can I compensate for saturation by changing the CT ratio setting?\", \"acceptedAnswer\": {\"@type\": \"Answer\", \"text\": \"No. A ratio setting does not restore missing or distorted waveform information. Establish whether the problem is a fixed scaling mismatch, a sensor limitation, burden, or another signal-chain issue before choosing a remedy.\"}}, {\"@type\": \"Question\", \"name\": \"Can the same CT be used for an AHF and another instrument?\", \"acceptedAnswer\": {\"@type\": \"Answer\", \"text\": \"Only if the complete arrangement is explicitly supported by the relevant equipment specifications and approved design. Evaluate input compatibility, wiring, total burden, and safety requirements; do not add a device to an existing secondary circuit by assumption.\"}}, {\"@type\": \"Question\", \"name\": \"Is an AHF stop command enough before disconnecting CT leads?\", \"acceptedAnswer\": {\"@type\": \"Answer\", \"text\": \"No. Stopping compensation does not establish isolation of the primary conductor or the sensing circuit. Follow the installation's approved CT safety and electrical isolation procedures before disturbing any connections.\"}}]}<\/script><\/p>\n","protected":false},"excerpt":{"rendered":"<p>Distinga a satura\u00e7\u00e3o dos TC dos erros de rela\u00e7\u00e3o de transforma\u00e7\u00e3o, largura de banda e realimenta\u00e7\u00e3o antes de alterar um filtro harm\u00f3nico ativo. Inclui verifica\u00e7\u00f5es da carga e da forma de onda.<\/p>","protected":false},"author":4,"featured_media":3991,"comment_status":"open","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"_gspb_post_css":"","footnotes":""},"categories":[1],"tags":[219],"class_list":["post-3994","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-blog","tag-active-harmonic-filter"],"blocksy_meta":{"styles_descriptor":{"styles":{"desktop":"","tablet":"","mobile":""},"google_fonts":[],"version":8}},"acf":[],"amp_enabled":true,"_links":{"self":[{"href":"https:\/\/cnbygele.com\/pt\/wp-json\/wp\/v2\/posts\/3994","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/cnbygele.com\/pt\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/cnbygele.com\/pt\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/cnbygele.com\/pt\/wp-json\/wp\/v2\/users\/4"}],"replies":[{"embeddable":true,"href":"https:\/\/cnbygele.com\/pt\/wp-json\/wp\/v2\/comments?post=3994"}],"version-history":[{"count":1,"href":"https:\/\/cnbygele.com\/pt\/wp-json\/wp\/v2\/posts\/3994\/revisions"}],"predecessor-version":[{"id":3995,"href":"https:\/\/cnbygele.com\/pt\/wp-json\/wp\/v2\/posts\/3994\/revisions\/3995"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/cnbygele.com\/pt\/wp-json\/wp\/v2\/media\/3991"}],"wp:attachment":[{"href":"https:\/\/cnbygele.com\/pt\/wp-json\/wp\/v2\/media?parent=3994"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/cnbygele.com\/pt\/wp-json\/wp\/v2\/categories?post=3994"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/cnbygele.com\/pt\/wp-json\/wp\/v2\/tags?post=3994"}],"curies":[{"name":"bem jogado","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}