Reactive Power Compensator

GJ19 Series Switching Capacitor Contactor

CJ19series switching capacitor contactors (hereinafter referred to as contactors) are mainly used in power lines with AC 50Hz or 60Hz and rated working voltage up to 400V, for the use of low-voltage reactive power compensation equipment to input or remove low-voltage parallel capacitors. The contactor is equipped with a surge suppression device, which can effectively reduce the impact of closing surge on the capacitor and suppress over voltage during opening and closing.

Overview
Downloads

Structural Characteristics

The contactor is a direct acting double break point structure, and the contact system is arranged in two layers. The upper layer has three pairs of current limiting contacts and a current limiting resistor to form a surge suppression device. When it is closed, it is first connected for a few miliseconds before the working contact is connected. The permanent magnetic block in the current limiting contact is released under the reaction of the spring, disconnecting the current limiting resistor and allowing the capacitor to work normally. The internal circuit connection diagram of the contactor (see figure).

The contactors of CJ19-25-43 have two pairs of auxiliary contacts, while the contactors of CJ19-63-95 have three pairs of auxiliary contacts. The terminal of the contactor is covered with an insulation cover, ensuring safety and reliability. The coil terminals are marked with voltage data to prevent incorrect connections. The CJ19-25-43 contactor can be installed with screws or can be fastened onto a 35mm standard clamp rail using the slider at the bottom. There is a detachable rectanqular white plaque on the mask, which users can use to print project codes,etc. CJ19-63-95 can be installed with 35mm or 75mm standard clamp rails.

Specification

Product model name CJ19-25 CJ19-32 CJ19-53 CJ19-63 CJ19-95
Electrical life (10000 cycles) 10 10 10 10 10
Rated current le (380V)A 17 23 29 43 63
Controllable capacitor
capacity(kvar)
220V 6 9 10 15 22
380V 12 18 20 30 40
Rated insulation voltage (V) 500 500 500 500 500
Surge suppression capability 20le 20le 20le 20le 20le
Action conditions Actuation:(85%~110%)Us;Release:(20%~75%)Us
Coil power (VA)start/hold  70/8  110/11  110/11  200/20  200/20
Auxiliary contact control capacity AC-15 360VA;DC-3 33W
Weight(kg) 0.44 0.63 0.64 1.4 1.5

Appearance And Installation Dimensions

CJ19-25~43 Contactor appearance and installation dimensions

Model Amax Bmax Cmax Dmax E F Notes
CJ19-25 80 47 124 76 34/35 50/60 In addition to screw installation.
a 35mm mounting rail can also be
used for installation
CJ19-32 90 58 132 86 40 48
CJ19-43 90 58 136 86 40 48

CJ19-63~95 Contactor appearance and installation dimensions

Model Amax Bmax Cmax Notes
CJ19-63 132 79 150 In addition to screw installation,35mm and 75mm mounting rails can also be used for installation
CJ19-95 135 87 158

Ordering Instructions

  • When ordering, it is necessary to indicate the complete name and model of the contactor;
  • The rated control power supply voltage and frequency of the coil; Order quantity.
  • Ordering example: CJ19-43/11Switching capacitor contactor coil voltage220V 50Hz10units.